Boiler Amine M406
Boiler Amine M406
Boiler Amine M406
Boiler Amine M406

Boiler Amine M406

Quoted by volume and application · SKU BA406000
Size

Pricing and lead time within one business day.

Prevent corrosion and protect steam and condensate lines. Boiler Amine M-406 is a proprietary blend of neutralizing amines designed to control corrosion caused by carbon dioxide in steam and condensate systems. It neutralizes acidic condensate and raises pH throughout the return network, protecting system piping, traps, and heat exchangers from corrosion. This versatile formula distills with the steam to provide continuous protection from the boiler through the condensate return line.  Key Benefits  Prevents corrosion caused by CO₂ and acidic condensate  Maintains system pH between 8.0 and 9.0 for optimal protection  Provides protection for short and long condensate return systems  Reduces maintenance and extends equipment life  Where to Use  Steam boilers and condensate return systems  Deaerators and feedwater systems  Product Details  Type: Corrosion inhibitor  Form: Liquid  Color / Appearance: Light blue liquid  pH Range: 11–12 (1% solution)  Dosing & Application  Feed Rate: Add 1 quart per 150 ppm CO₂ per 1,000 gallons of makeup water.  Target pH: Maintain condensate return pH between 8.0 and 9.0.  Feed Method: Apply to the deaerator, feedwater system, boiler, or directly into the steam header.  Control Equipment: Use a variable output positive displacement pump for consistent dosing.  Alternative Feed: In some systems, chemical can be added via shot feeding through a pot-type feeder.  Packaging Options  Available in 1-gallon jug, 5-gallon pails, 15-gallon drums, and 30-gallon drums  Bulk delivery available upon request